• DocumentCode
    510994
  • Title

    Discussions on post arc current of a CO2 circuit breaker

  • Author

    Nishiwaki, S. ; Koshizuka, T. ; Uchii, T. ; Kawano, H.

  • Author_Institution
    Toshiba Corp., Kawasaki, Japan
  • fYear
    2008
  • fDate
    7-12 Sept. 2008
  • Firstpage
    125
  • Lastpage
    128
  • Abstract
    It has been observed in our tests that the post arc current near the breaking limit of a CO2 circuit breaker is 10 A or more, and the post arc current of a SF6 circuit breaker is approximately 0.3 A. We explain this major difference in the post arc current with calculations using two serially-connected arc models. We prove that the arc characteristic of a relatively longer time domain up to the extinction peak for a CO2 circuit breaker and that of a short time domain from the extinction peak until the current zero point for a SF6 circuit breaker have great effects on breaking performance.
  • Keywords
    SF6 insulation; circuit breakers; circuit-breaking arcs; gas blast circuit breakers; CO2 circuit breaker; SF6 circuit breaker; current zero point; post arc current; serially-connected arc models calculation; Circuit breakers; Circuit testing; Current measurement; Equations; Linear approximation; Substations; Sulfur hexafluoride; Time measurement; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
  • Conference_Location
    Cardiff
  • Print_ISBN
    978-0-9558052-0-2
  • Type

    conf

  • Filename