• DocumentCode
    541246
  • Title

    Protection performance analysis and settings during power black-start of northern Jiangsu district

  • Author

    Cui, Yu ; Yan, Guo-ping ; Liu, Jin-guan

  • Author_Institution
    Jiangsu Electr. Power Co., Nanjing, China
  • fYear
    2010
  • fDate
    13-16 Sept. 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    By analyzing features of the power black-start system of northern Jiangsu district, the line current differential protection was set as the main protection for black-start path. Based on analysis of failure of black-start system, the fault current and voltage were verified to meet the distance and zero-sequence protection requirements. Furthermore, problems and solutions of back-up distance protection in the black-start system were particularly analyzed.
  • Keywords
    fault currents; power system protection; Jiangsu; back-up distance protection; black-start path; fault current; line current differential protection; power black-start system; protection performance analysis; zero-sequence protection requirements; Circuit faults; Current measurement; Fault currents; Generators; Optical fiber devices; Power generation; Power systems; Black-start; failure analysis; line protection; relay setting;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2010 China International Conference on
  • Conference_Location
    Nanjing
  • Print_ISBN
    978-1-4577-0066-8
  • Type

    conf