• DocumentCode
    570327
  • Title

    Transformer core accidents caused by loosing ground wire

  • Author

    Qinghao, Wang ; Hua, Zhang ; Guobin, Liu ; Wenguang, Zhang ; Na, Li ; Ying, Yang ; Guohai, Ma

  • Author_Institution
    Fushun Power Supply Co., Fushun, China
  • fYear
    2012
  • fDate
    21-24 May 2012
  • Firstpage
    1
  • Lastpage
    3
  • Abstract
    The paper describes grounding wire of transformer core becomes flexible, leads to the core produce suspended potential, results in discharge, the discharge current is generated power loss in the ground copper and the ground lead of the core, and causes transformer oil chromatographic analysis data anomalies. Put forward when the total hydrocarbons increases but not “out of limits”, the searching method for fault reasons, steps and precautions, noting that the external ground wire of transformer core is loosing also belongs to the category of the core faults.
  • Keywords
    discharges (electric); search problems; transformer oil; wires (electric); discharge current; ground copper; ground lead; hydrocarbons; power loss; searching method; transformer core accidents; transformer core external ground wire; transformer oil chromatographic analysis data anomalies; Circuit faults; Discharges (electric); Grounding; Oil insulation; Power transformer insulation; Transformer cores; Wires; chromatographic analysis; core; grounding; suspended discharge;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies - Asia (ISGT Asia), 2012 IEEE
  • Conference_Location
    Tianjin
  • Print_ISBN
    978-1-4673-1221-9
  • Type

    conf

  • DOI
    10.1109/ISGT-Asia.2012.6303143
  • Filename