• DocumentCode
    602428
  • Title

    Transformer sympathetic inrush: A case study

  • Author

    Tsourakis, G. ; Milis, I. ; Prousalidis, John

  • Author_Institution
    PROT.A.S.I.S (PROTection Applic. & Studies - Ind. Services) SA, Athens, Greece
  • fYear
    2012
  • fDate
    1-3 Oct. 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Transformer sympathetic inrush has been analyzed in the literature but is often not highly appreciated. The loss of several motors of a large refinery in Greece, following the energization of the step-up transformer of a nearby new electric power plant, initiated the investigation of the associated transient phenomena. An EMT model of the power system under study has been developed and validated using recordings of the transformer current inrush. Connection modifications are investigated to reduce the impact of the power plant transformer energization to the refinery´s power system.
  • Keywords
    electric motors; power plants; power transformers; EMT model; Greece; electric power plant; motors; power plant transformer energization; power system; refinery power system; step-up transformer; transformer current inrush; transformer sympathetic inrush; EMTP; switching transients; sympathetic inrush;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Generation, Transmission, Distribution and Energy Conversion (MEDPOWER 2012), 8th Mediterranean Conference on
  • Conference_Location
    Cagliari
  • Electronic_ISBN
    978-1-84919-715-1
  • Type

    conf

  • DOI
    10.1049/cp.2012.2053
  • Filename
    6521895