• DocumentCode
    615639
  • Title

    Incapability of analog relay protection to detect generator stator winding ground failures at neutral end

  • Author

    Maughan, Clyde V.

  • Author_Institution
    Maughan Generator Consultants, Schenectady, NY, USA
  • fYear
    2013
  • fDate
    2-5 June 2013
  • Firstpage
    490
  • Lastpage
    493
  • Abstract
    The electromechanical ground protection relay 59GN commonly used in generator protection does not respond to grounds in the bottom ~5% of the stator winding. Recent experience with 4 such failures to large generators suggests that this lack of protection can be a disastrous deficiency. These 4 failures each caused massive damage to the generator, and collectively had a total cost, including repair and loss of generation, close to $500,000,000. This paper will describe those 4 failures, and will discuss newer ground relay systems that monitor and protect the entire stator winding for grounds. The objective of this paper is to encourage owner/operators to add one of the newer relay systems.
  • Keywords
    power generation faults; power generation protection; relay protection; stators; 59GN relay; analog relay protection; electromechanical ground protection relay; generator protection; generator stator winding ground failure detection; ground relay system; stator winding monitoring; stator winding protection; Generators; Harmonic analysis; Insulation; Power system harmonics; Relays; Stator windings; Windings; generator stator winding; ground relay protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference (EIC), 2013 IEEE
  • Conference_Location
    Ottawa, ON
  • Print_ISBN
    978-1-4673-4738-9
  • Electronic_ISBN
    978-1-4673-4739-6
  • Type

    conf

  • DOI
    10.1109/EIC.2013.6554296
  • Filename
    6554296