  • Abstract
    In this paper, we propose a method to optimally set the taps of voltage regulation transformers in distribution networks. Specifically, we cast the problem of optimally choosing the tap settings as a rank-constrained semidefinite program (SDP) with the transformer tap positions removed from the network´s admittance matrix and replaced by additional constraints and optimization variables. Then, the non-convex rank-1 constraint that arises from this rank-constrained SDP formulation is relaxed, which leads to a convex SDP program. The tap positions are obtained from the primary- and secondary-side bus voltages yielded by the optimal solution. We present several case studies with a 14-bus single-phase and a 15-bus three-phase distribution system to demonstrate the validity of our method.
  • Keywords
    distribution networks; mathematical programming; power transformers; voltage control; SDP; distribution networks; network admittance matrix; nonconvex rank-1 constraint; optimal tap settings; primary-side bus voltages; rank-constrained semidefinite program; secondary-side bus voltages; transformer tap positions; voltage regulation transformers; Admittance; Impedance; Mathematical model; Optimization; Power transmission lines; Silicon; Voltage control; Optimal Power Flow (OPF); Semidefinite Programming (SDP); Tap-Changing under-load (TCUL) transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    North American Power Symposium (NAPS), 2013
  • Conference_Location
    Manhattan, KS
  • Type

    conf

  • DOI
    10.1109/NAPS.2013.6666885
  • Filename
    6666885