DocumentCode
647689
Title
Simulation of transformer hot-spot heating due to Geomagnetically Induced Currents
Author
Marti, L. ; Rezaei-Zare, Afshin ; Narang, Arun
Author_Institution
Hydro One Networks Inc., Toronto, ON, Canada
fYear
2013
fDate
21-25 July 2013
Firstpage
1
Lastpage
1
Abstract
Summary form only given. This paper proposes a method to estimate transformer hot-spot heating due to half-cycle saturation caused by Geomagnetically Induced Currents (GIC). The method is based on fitting a closed-form analytical function to the calculated or measured thermal response of a particular transformer design, typically provided by the manufacturer, at its hotspot locations to a step dc current excitation. This fitted function can then be used to simulate the hotspot temperature profile for transformers of that particular design when subjected to GIC having an arbitrary profile over time. Using this approach, examples are presented of the winding and metallic hot-spot thermal responses of two transformers to recorded GIC time sequences, to illustrate how hot-spots may be impacted on during a Geomagnetic Disturbance (GMD) event.
Keywords
geomagnetism; temperature measurement; transformer windings; closed-form analytical function; geomagnetic disturbance event; geomagnetically induced currents; half-cycle saturation; hotspot location; hotspot temperature profile; metallic hot-spot thermal response; step dc current excitation; transformer design; transformer hot-spot heating; transformer winding; Circuit faults; Current measurement; Fitting; Heating; Temperature measurement; Thermal analysis; Windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location
Vancouver, BC
ISSN
1944-9925
Type
conf
DOI
10.1109/PESMG.2013.6672213
Filename
6672213