• DocumentCode
    684180
  • Title

    The effect of Applied-voltage on photon-number of corona discharge on transmission lines defect

  • Author

    Wan Shuwei ; Zhao Xuesong ; Guo Xinyang ; Chen Lan ; Bian Xingming ; Yao Wenjun ; Macalpine, Mark ; Wang Liming ; Guan Zhicheng

  • Author_Institution
    State Grid Chongqing Nan´an Power Supply Co., Chongqing, China
  • fYear
    2013
  • fDate
    20-23 Oct. 2013
  • Firstpage
    311
  • Lastpage
    314
  • Abstract
    Defects of high-voltage transmission lines are often accompanied with corona discharge; and corona discharge would produce ultraviolet. Based on this principle, the UV imager can be used in detecting the defect. Electric field strength is the main factor affecting the corona discharge, which is determined by power-supply and experimental model. In this paper, UV measurement of different defects was studied, and the effect of Applied-voltage on corona discharge of defects was acquired. A quadratic relationship exists between the UV strength produced by corona discharge and applied voltage. The quadratic coefficient A is between 0.31~0.37, which is increase with the length increasing at the experimental conditions in this paper.
  • Keywords
    corona; discharges (electric); power transmission lines; UV measurement; applied-voltage effect; defect corona discharge; photon-number; transmission lines defect; ultraviolet measurement; Companies; Conductors; Corona; Discharges (electric); Photonics; Power transmission lines; Transmission line measurements; UV characteristics; corona discharge; defect; photon-number; transmission line;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
  • Conference_Location
    Shenzhen
  • Type

    conf

  • DOI
    10.1109/CEIDP.2013.6748269
  • Filename