• DocumentCode
    717253
  • Title

    System Static Safety Analysis Under Multi-UHVDC Hierarchically Infeed Mode

  • Author

    Ye Guan-hao ; Zhang Yan

  • Author_Institution
    Sch. Of Electron. Inf. & Electr. Eng., Shanghai Jiao Tong Univ., Shanghai, China
  • fYear
    2015
  • fDate
    10-12 Feb. 2015
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    Based on the concept of “Multi-Infeed Short Circuit Ratio” (MISCR) CIGRE proposed, the paper focuses on analysing static security of UHV AC-DC hybrid system under three infeed modes of 2 UHVDC (±800 kV) lines: 2 UHVDC lines completely feeding in UHVAC (1000kV) system, completely feeding in EHVAC (500kV) system and feeding in these two levels of AC system hierarchically. Firstly, the value of “MISCR” is calculated respectively under these infeed modes. Secondly, constant voltage of AC system which UHVDC lines feed in is analysed, the relationship between constant voltage, “MISCR” and different infeed modes is discussed. Thirdly, Self-organized method is used to find limit DC power under different infeed modes. Finally, some China sectional power grid where UHVDC lines feed in is taken as an example, simulation is carried out and theories proposed get verified.
  • Keywords
    HVDC power transmission; safety; AC system; CIGRE; China sectional power grid; EHVAC system; MISCR; constant voltage; multi-UHVDC hierarchically infeed mode; multiinfeed short circuit ratio; self-organized method; static security; system static safety analysis; Constant voltage; Infeed mode; Limit power; MISCR; UHV;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    AC and DC Power Transmission, 11th IET International Conference on
  • Conference_Location
    Birmingham
  • Print_ISBN
    978-1-84919-982-7
  • Type

    conf

  • DOI
    10.1049/cp.2015.0098
  • Filename
    7140580