Transformer incipient inter-turn fault detection based on no-load current harmonic analysis
Author
Venikar, P.A. ; Ballal, M.S. ; Umre, B.S. ; Suryawanshi, H.M.
Author_Institution
Dept. of Electr. Eng., Visvesvaraya Nat. Inst. of Technol., Nagpur, India
fYear
2015
fDate
June 29 2015-July 2 2015
Firstpage
1
Lastpage
5
Abstract
This paper presents use of no-load current harmonic analysis to detect presence of inter-turn fault at incipient stage. At steady state, third and fifth harmonic components are predominant in transformer no-load current. Inception of fault results in decrease in THD and increase in increase in primary current. Based on reduction of total harmonic distortion (THD) of each phase and simultaneous increase in primary current, it is possible do detect presence of inter-turn fault. Wavelet analysis is also performed to validate the results. Proposed method offers higher sensitivity and accuracy as it can detect fault at incipient stage involving less than 2% turns and fault current up-to 1 p.u.
Keywords
fault diagnosis; harmonic analysis; harmonic distortion; power transformers; no-load current harmonic analysis; total harmonic distortion; transformer incipient inter-turn fault detection; wavelet analysis; Circuit faults; Fault currents; Harmonic analysis; Phase transformers; Power transformers; Wavelet analysis; Windings; Fourier transform; harmonic analysis; incipient inter-turn fault; transformer no-load current; wavelet analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
PowerTech, 2015 IEEE Eindhoven
Conference_Location
Eindhoven
Type
conf
DOI
10.1109/PTC.2015.7232294
Filename
7232294
Link To Document