Reduced DC circuit breaker requirement on mixed converter HVDC networks
Author
Chaffey, Geraint ; Green, Tim C.
Author_Institution
Electrical and Electronic Engineering Department, Imperial College London, UK
fYear
2015
fDate
June 29 2015-July 2 2015
Firstpage
1
Lastpage
6
Abstract
Recently proposed meshed HVDC networks include both converters and DC circuit breakers, and the fault currents experienced and therefore the capacity requirement of circuit breakers are dependent on the topology of converters used on the network. This paper analyses the difference in fault currents seen in various network configurations utilising fault-feeding and fault-blocking converters. Results are presented showing the reduced fault currents seen in the regions of the DC network where fault current limiting converters have been implemented, which could have an impact on the topology, current rating and therefore size and cost of the circuit breaker.
Keywords
Circuit breakers; Circuit faults; Fault currents; HVDC transmission; Network topology; Power cables; Topology; AC-DC power converters; Circuit breakers; Fault protection; HVDC transmission;