• DocumentCode
    750783
  • Title

    105°C/140°C rated EPR insulated power cables

  • Author

    Cinquemani, Paul L. ; Kuchta, Frank L. ; Rahman, Mujibar M. ; Ruffinazzi, Franco ; Zaopo, Antonio

  • Author_Institution
    Pirelli Cable Corp., Lexington, SC, USA
  • Volume
    11
  • Issue
    1
  • fYear
    1996
  • fDate
    1/1/1996 12:00:00 AM
  • Firstpage
    31
  • Lastpage
    42
  • Abstract
    The excellent long-term operation and field performance of existing EPR cables under the current industry operating temperatures of 90°C normal and 130°C overload is well known. This paper describes a study for the implementation of a higher temperature rated EPR cable system including accessories up to a range of 105°C continuous service and 140°C emergency operation. The investigation has been carried out into the electrical, mechanical, and thermal behavior of the system as a function of temperature. Compatibility has been studied under higher temperature in relation to conductor filling compound and the semi-conducting stress control layer. The results indicate that insulation degradation does not occur under accelerated and elevated temperature testing, concluding that properly formulated and selected materials are both compatible and suitable for the higher temperature ratings
  • Keywords
    ageing; cable jointing; ethylene-propylene rubber; insulation testing; life testing; power cable insulation; power cable testing; power cables; thermomechanical treatment; 105 to 140 C; EPR insulated power cables; ampacity ratings; cable splices; cable terminations; conductor filling compound; continuous service; electrical testing; emergency operation; insulation degradation; semi-conducting stress control layer; thermal ageing; thermomechanical testing; voltage life testing; wet ageing; Cable insulation; Conducting materials; Filling; Life estimation; Materials testing; Paramagnetic resonance; Power cables; Stress control; Temperature distribution; Thermal degradation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.483998
  • Filename