• DocumentCode
    751009
  • Title

    Insulation characteristics of GIS spacer for very fast transient overvoltage

  • Author

    Okabe, S. ; Koto, M. ; Endo, F. ; Kobayashi, K.

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    11
  • Issue
    1
  • fYear
    1996
  • fDate
    1/1/1996 12:00:00 AM
  • Firstpage
    210
  • Lastpage
    218
  • Abstract
    V-t characteristics of spacer surfaces for VFT were investigated under particle contaminated conditions for gas insulated switchgear (GIS). V-t characteristics for VFT were measured with the particle length, oscillation frequency, amplitude, and damping factor of VFT waveform as parameters. Differences in V-t characteristics for VFT due to variation of oscillation frequency, amplitude, and damping factor were small. Further, they were compared with V-t characteristics for lightning impulse. The dielectric strength of spacer surfaces for VFT was found to be at least equivalent to the dielectric strength for lightning impulse
  • Keywords
    damping; electric strength; gas insulated switchgear; insulation testing; lightning; overvoltage; switchgear testing; transient analysis; voltage measurement; GIS spacer; V-t characteristics; VFT waveform; amplitude; damping factor; dielectric strength; gas insulated switchgear; lightning impulse; oscillation frequency; particle contaminated conditions; particle length; spacer surfaces; very fast transient overvoltage; Damping; Dielectric breakdown; Dielectric measurements; Frequency measurement; Gas insulation; Geographic Information Systems; Length measurement; Lightning; Surface contamination; Switchgear;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.484018
  • Filename