DocumentCode
758547
Title
Fuzzy-logic-based fault classification scheme for digital distance protection
Author
Das, Biswarup ; Reddy, J. Vittal
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol., Roorkee, India
Volume
20
Issue
2
fYear
2005
fDate
4/1/2005 12:00:00 AM
Firstpage
609
Lastpage
616
Abstract
In this paper, a fuzzy-logic-based algorithm to identify the type of faults for digital distance protection system has been developed. The proposed technique is able to accurately identify the phase(s) involved in all ten types of shunt faults that may occur in a transmission line under different fault resistances, inception angle, and loading levels. The proposed method needs only three line-current measurements available at the relay location and can perform the fault classification task in about a half-cycle period. Thus, the proposed technique is well suited for implementation in a digital distance protection scheme.
Keywords
fault location; fuzzy logic; power transmission faults; power transmission lines; power transmission protection; digital distance protection; fault classification; fault resistance; fuzzy logic; line current measurement; relay location; shunt fault; transmission line; Digital relays; Fault diagnosis; Fuzzy logic; Fuzzy systems; Hybrid intelligent systems; Power system protection; Power system relaying; Power system reliability; Power transmission; Protective relaying; Fault classification; fuzzy logic; power transmission;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.834294
Filename
1413293
Link To Document