DocumentCode
775042
Title
A reiterative DFT to damp decaying DC and subsynchronous frequency components in fault current
Author
Yu, Chi-Shan
Author_Institution
Dept. of Electr. Eng., Chung Cheng Inst. of Technol., Taoyuan
Volume
21
Issue
4
fYear
2006
Firstpage
1862
Lastpage
1870
Abstract
This work presents a reiterative discrete Fourier transform (DFT) algorithm for fault current filtering. First, the short-windows DFT (SWDFT)-based mimic filter is developed to damp the measurement. Then, a reiterative scheme is proposed to reconstruct the damped measurement for further damping. The proposed algorithm can sufficiently damp the decaying dc as well as the subsynchronous frequency components. Thus, the proposed algorithm is appropriate to the filtering design on both the conventional and series-compensated transmission lines. Meanwhile, the recursive form is developed to reduce the computational burden. The simulation results illustrate that the algorithm significantly reduces the time to obtain the accurate fundamental phasor and that it has a better performance than the conventional DFT algorithm
Keywords
digital filters; discrete Fourier transforms; fault currents; power transmission faults; power transmission protection; relay protection; decaying dc damping; fault current filtering; mimic filter; reiterative discrete Fourier transform algorithm; series-compensated transmission lines; subsynchronous frequency components; Damping; Discrete Fourier transforms; Fault currents; Filtering algorithms; Frequency estimation; Frequency measurement; Noise measurement; Power harmonic filters; Power system transients; Transmission line measurements; Damping; decaying dc component; discrete Fourier transform (DFT); mimic filter; subsynchronous frequency component;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2006.877082
Filename
1705542
Link To Document