DocumentCode
784561
Title
Selection and application of relay protection for six phase demonstration project
Author
Rebbapragada, R.V. ; Panke, H. ; Pierce, H.J., Jr. ; Stewart, J.R. ; Oppel, L.J.
Author_Institution
ebasco Services Inc., Lyndhurst, NJ, USA
Volume
7
Issue
4
fYear
1992
fDate
10/1/1992 12:00:00 AM
Firstpage
1900
Lastpage
1911
Abstract
The protection and control requirements needed for a 115 kV line after it was reconfigured to operate as a single-circuit six-phase line as part of a high-phase-order demonstration project are discussed. Addressed are the required modification and/or additions needed for the existing protection and control equipment. The criteria selected for the protection of the transmission line are described, including the transformers required for six-phase reconfiguration. The commercially available digital protection systems applicable to the protection of the line and their limitations are reviewed. Requirements for protection and control panels, their location for optimal wiring, and facilities to perform tests and measurements are also covered
Keywords
power system control; power system protection; power transmission lines; relay protection; 115 kV; control panels; digital protection systems; high-phase-order; optimal wiring; relay protection; single-circuit six-phase line; six phase demonstration project; transformers; transmission line; Circuit faults; Control equipment; Digital relays; Optimal control; Power system protection; Power transmission lines; Protective relaying; Substation protection; Transformers; Wiring;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.156993
Filename
156993
Link To Document