Capacitor switching capability of vacuum interrupter with CuW contact material
Author
Yokokura, K. ; Matsuda, M. ; Atsumi, K. ; Miyazawa, T. ; Sohma, S. ; Kaneko, E. ; Ohshima, I.
Author_Institution
Toshiba Corp., Tokyo, Japan
Volume
10
Issue
2
fYear
1995
fDate
4/1/1995 12:00:00 AM
Firstpage
804
Lastpage
810
Abstract
The authors carried out shunt capacitor switching tests on 24 kV model vacuum interrupters with contact materials CuW and CuCr. The restriking probability of the contact material CuW is lower than that of CuCr. The contact material CuW is also an excellent candidate for shunt capacitor switching except for its high current interruption ability. The restriking probability of a 24 kV, 25 kA vacuum interrupter with contact material CuW is calculated as 10-5, which is practically zero
Keywords
chromium alloys; copper alloys; electrical contacts; power capacitors; probability; restriking voltage; switchgear testing; tungsten alloys; vacuum circuit breakers; vacuum interrupters; 24 kV; 25 kA; CuCr; CuW; capacitor switching capability; contact material; high current interruption ability; restriking probability; shunt capacitor switching tests; vacuum interrupter; Circuit breakers; Circuit testing; Contacts; Frequency; Interrupters; Materials testing; Power distribution; Surges; Switched capacitor circuits; Switching circuits;