• DocumentCode
    822240
  • Title

    Implicitly constrained substation model for state estimation

  • Author

    De La Villa Jaén, Antonio ; Gómez-Expósito, Antonio

  • Author_Institution
    Dept. of Electr. Eng., Seville Univ., Spain
  • Volume
    17
  • Issue
    3
  • fYear
    2002
  • fDate
    8/1/2002 12:00:00 AM
  • Firstpage
    850
  • Lastpage
    856
  • Abstract
    This paper addresses the problem of including detailed substation models in state estimation at the least possible cost. After reviewing existing alternatives, it is shown how Lagrange multipliers associated with topological constraints can be easily computed from an implicit model the size of which is slightly larger than that of the conventional bus-branch approach. This allows bad data and topological error processing to be carried out simultaneously.
  • Keywords
    control system analysis; energy management systems; power system control; power system state estimation; substations; Lagrange multipliers; bad data processing; implicitly constrained substation model; power systems; state estimation; topological constraints; topological error processing; Circuit breakers; Computer errors; Costs; Load flow; Medical services; Redundancy; State estimation; Substations; Topology; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2002.800979
  • Filename
    1033735