• DocumentCode
    824338
  • Title

    Multi-inverter UPS system with redundant load sharing control

  • Author

    Holtz, Joachim ; Werner, Karl-Heinz

  • Author_Institution
    Wuppertal Univ., Germany
  • Volume
    37
  • Issue
    6
  • fYear
    1990
  • fDate
    12/1/1990 12:00:00 AM
  • Firstpage
    506
  • Lastpage
    513
  • Abstract
    The concept of a redundant multi-inverter UPS (uninterruptible power supply) system which includes extended monitoring of the status and the operating conditions of all power electronic equipment is described. Each block of the UPS system is monitored by two independent microcomputers that process the same data. The microcomputers are part of a redundant distributed monitoring system that is separately interlinked by two serial data buses through which they communicate. They establish a hierarchy among the participating blocks by defining one of the healthy inverter blocks as the master. The actual master runs the central synchronizing unit for the entire system, whereas the slave units perform the control of equal active and reactive load sharing. Operation and fault detection are experimentally illustrated in a dual inverter system with a rating of 10 kVA of redundant power
  • Keywords
    computerised control; computerised monitoring; invertors; load (electric); microcomputer applications; power engineering computing; uninterruptible power supplies; 10 kVA; distributed monitoring system; fault detection; microcomputer monitors; multi-inverter UPS; redundant load sharing control; serial data buses; uninterruptible power supply; Centralized control; Condition monitoring; Control systems; Data buses; Fault detection; Inverters; Master-slave; Microcomputers; Power electronics; Uninterruptible power systems;
  • fLanguage
    English
  • Journal_Title
    Industrial Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0278-0046
  • Type

    jour

  • DOI
    10.1109/41.103455
  • Filename
    103455