• DocumentCode
    847814
  • Title

    Behavior of the hydro-quebec 735-kV system under transient short-circuit conditions and its digital computer simulation

  • Author

    Malewski, Ryszard ; Narancic, Vojislav N. ; Robichaud, Yvan

  • Author_Institution
    Hydro-Quebec Institute of Research, Varennes, Quebec, Canada
  • Volume
    94
  • Issue
    2
  • fYear
    1975
  • fDate
    3/1/1975 12:00:00 AM
  • Firstpage
    425
  • Lastpage
    431
  • Abstract
    Five single-phase short-circuit tests were performed on the live 735-kV system. Transient currents and voltages were recorded on magnetic tape. The transmission system under fault conditions was simulated on a digital computer. The measured and simulated transients were superimposed on the same graphs using a computer-controlled plotter. The accuracy of measurements was evaluated and the graphs of the simulated transients were compared with those of the measured ones. This comparative study was then used for an experimental check of the computer simulation and provided reassurance that the system modeling was precise enough for further transient analyses.
  • Keywords
    Area measurement; Computational modeling; Computer simulation; Power system transients; Resistors; Substations; System testing; Transient analysis; Transmission line measurements; Voltage;