• DocumentCode
    847846
  • Title

    Influence of the delay of the first corona pulse on the switching impulse breakdown probability

  • Author

    Menemenlis, C. ; Anis, H.

  • Author_Institution
    Hydro-Quebec Institute of Research, Varennes, Quebec, Canada
  • Volume
    94
  • Issue
    2
  • fYear
    1975
  • fDate
    3/1/1975 12:00:00 AM
  • Firstpage
    455
  • Lastpage
    466
  • Abstract
    Tests with a rod-plane gap with a rounded termination of the rod show that the delay of the first corona pulse affects the positive switching impulse breakdown probability. The inverted S form or local inconsistencies of the breakdown probability distribution are connected with particular statistical features of the delay of the first corona pulse. The influence of the rod termination or the impulse front on the breakdown probability distribution is explained in terms of the delay of the first corona pulse.
  • Keywords
    Breakdown voltage; Corona; Delay; Electric breakdown; Electrodes; IEEE members; Impulse testing; Insulation; Probability distribution; Pulse shaping methods;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.31872
  • Filename
    1601474