DocumentCode
848596
Title
Effects of arcs in enclosures filled with SF6 and steps taken to restrict them in SF6 switchgear
Author
Strasser, H. ; Schmidt, K.D. ; Högg, P.
Author_Institution
Brown, Boveri Baden, Switzerland
Volume
94
Issue
3
fYear
1975
fDate
5/1/1975 12:00:00 AM
Firstpage
1051
Lastpage
1060
Abstract
For internal arc faults in metalclad SF6 switchgear the main parameters fault current, arc voltage, fault duration, enclosed volume and material of the enclosure are discussed in relation to test results. The effects in connection with pressure rise and melting through are stated, from which the requirements to be complied with by SF6 installations are derived. Measures to restrict the effects of arc faults are compared and a solution deduced which satisfies the requirements imposed.
Keywords
Dielectric breakdown; Dielectrics and electrical insulation; Fault currents; Inorganic materials; Monitoring; Power system reliability; Sulfur hexafluoride; Switchgear; Testing; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.31939