DocumentCode
852979
Title
Steep fronted surges applied to large AC motors-effect of surge capacitor value and lead length
Author
McLaren, P.G. ; Abdel-Rahman, M.H.
Author_Institution
Eng. Lab., Cambridge Univ., UK
Volume
3
Issue
3
fYear
1988
fDate
7/1/1988 12:00:00 AM
Firstpage
990
Lastpage
997
Abstract
The line end coil of large AC motors is known to suffer increased inter-turn voltage stress under steep fronted surge conditions. Surge capacitors can be used to slow down the surge rise-time. The effects of capacitor value and lead length on the line end coil voltage are examined. The theoretical and measured waveforms for the line end coil of a 3.3 kV, 1 MW, four-pole induction motor are compared. The results show clearly that when the capacitor lead length approaches 1, even a relatively large capacitor value has little effect
Keywords
induction motors; power capacitors; surge protection; surges; 1 MW; 3.3 kV; AC motors; four-pole induction motor; inter-turn voltage stress; lead length; line end coil; steep fronted surge conditions; surge capacitor value; Capacitors; Coils; Induction motors; Insulation; Nose; Stress; Surge protection; Transmission line matrix methods; Transmission line measurements; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.193878
Filename
193878
Link To Document