• DocumentCode
    853878
  • Title

    Post arc current of vacuum interrupter after large current interruption

  • Author

    Hakamata, Y. ; Kurosawa, Y. ; Natsui, K. ; Hirasawa, K. ; Kurita, K.

  • Author_Institution
    Hitachi Ltd., Tokyo, Japan
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1692
  • Lastpage
    1697
  • Abstract
    Postarc current characteristics of a vacuum interrupter have been examined under a condition of high-current interruption. A measurement technique was developed in which a shunt for measuring postarc current was set in a synthetic test circuit voltage source. Postarc current was measured after a 20-57 kA current interruption. The magnitude was greatly influenced by the rate of current decline. Residual resistance between electrodes was calculated from the measured values of recovery voltage and postarc current. The recovery of residual resistance was very rapid immediately after current zero and become slow later
  • Keywords
    circuit breakers; electric current measurement; vacuum apparatus; 20 to 57 kA; high-current interruption; postarc current measurement; recovery voltage; residual resistance; synthetic test circuit voltage source; vacuum interrupter; Circuit breakers; Circuit testing; Current measurement; Electrical resistance measurement; Electrodes; Interrupters; Mathematical model; Measurement techniques; Vacuum arcs; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.193973
  • Filename
    193973