DocumentCode
853878
Title
Post arc current of vacuum interrupter after large current interruption
Author
Hakamata, Y. ; Kurosawa, Y. ; Natsui, K. ; Hirasawa, K. ; Kurita, K.
Author_Institution
Hitachi Ltd., Tokyo, Japan
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
1692
Lastpage
1697
Abstract
Postarc current characteristics of a vacuum interrupter have been examined under a condition of high-current interruption. A measurement technique was developed in which a shunt for measuring postarc current was set in a synthetic test circuit voltage source. Postarc current was measured after a 20-57 kA current interruption. The magnitude was greatly influenced by the rate of current decline. Residual resistance between electrodes was calculated from the measured values of recovery voltage and postarc current. The recovery of residual resistance was very rapid immediately after current zero and become slow later
Keywords
circuit breakers; electric current measurement; vacuum apparatus; 20 to 57 kA; high-current interruption; postarc current measurement; recovery voltage; residual resistance; synthetic test circuit voltage source; vacuum interrupter; Circuit breakers; Circuit testing; Current measurement; Electrical resistance measurement; Electrodes; Interrupters; Mathematical model; Measurement techniques; Vacuum arcs; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.193973
Filename
193973
Link To Document