• DocumentCode
    853935
  • Title

    DC breaking tests up to 55 kA in a single vacuum interrupter

  • Author

    Benfatto, I. ; Maschio, A. ; Manganaro, S.

  • Author_Institution
    Istituto Gas Ionizzati, Padova, Italy
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1732
  • Lastpage
    1738
  • Abstract
    DC current breaking tests were carried out on several vacuum circuit-breakers during the design of the energy transfer units for the RFX fusion experiment. The tests were performed with a synthetic circuit able to reproduce the expected stresses on the switching element during the breaking phase. The performance of a prototype for a medium-voltage AC switch with a self-produced axial magnetic field is discussed. The interrupter was found capable of breaking currents up to 55 kA with a recovery voltage greater than 35 kV and high values of di/dt in a large range of arcing times
  • Keywords
    circuit breakers; testing; vacuum apparatus; 0 to 55 kA; 35 kV; DC current breaking tests; RFX fusion experiment; self-produced axial magnetic field; vacuum circuit-breakers; Circuit testing; Elementary particle vacuum; Energy exchange; Interrupters; Medium voltage; Performance evaluation; Prototypes; Stress; Switches; Switching circuits;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.193978
  • Filename