DocumentCode
853994
Title
Lightning induced failures in distributed transformers
Author
Puri, J.L. ; Abi-Samra, N.C. ; Dionise, T.J. ; Smith, D.R.
Author_Institution
Westinghouse Electr. Corp., Athens, GA, USA
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
1784
Lastpage
1801
Abstract
The findings of other investigators of transformer and distribution system response to lightning strokes are briefly reviewed and discussed. Digital studies performed to evaluate the effects of system and transformer parameters on service entrance phase-to-neutral voltage and on transformer currents due to lightning strokes are discussed. The effects of pertinent parameters are illustrated with curves. The results of full-scale tests confirming the digital simulations are presented. Based on this analysis, an approach for evaluating the impact of various low-voltage winding configurations on lightning-induced failures in distribution transformers is proposed
Keywords
distribution networks; lightning; power engineering computing; transformer testing; transformers; LV winding configurations; digital simulations; distributed transformers; full-scale tests; lightning induced failures; phase-to-neutral voltage; Circuit testing; Customer service; Digital simulation; Electrical equipment industry; Impulse testing; Lightning; Manufacturing; Surges; System testing; Transformer cores;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.193985
Filename
193985