DocumentCode
854179
Title
Effectiveness of zinc oxide surge arresters on substation equipment probabilities of flashover
Author
Lambert, Stephen R.
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
1928
Lastpage
1934
Abstract
Analyses indicate that significant differences can exist between effective probability of flashovers (PFOs) for a given insulation level, depending on whether surge arresters or circuit-breaker closing resistors are used to hold surges to about the same phase-to-ground levels. For phase-to-phase insulation, arresters are significantly less effective than circuit-breaker closing resistors at reducing PFOs. This is true for application of phase-to-ground arresters with or without phase-to-phase arresters. For phase-to-ground insulation, resistors are also more effective than arresters at reducing insulation requirements. This result is particularly applicable for station and line uprating and compact designs. Calculation techniques which consider phase-to-ground surges on all three phases, rather than techniques which simple consider only the phase which has the maximum surge, yield PFOs which more correctly represent the overall PFO of the insulation system
Keywords
flashover; substations; surge protection; zinc compounds; ZnO surge arresters; circuit-breaker closing resistors; flashover probabilities; phase-to-ground arresters; phase-to-ground levels; phase-to-phase arresters; phase-to-phase insulation; substation equipment; Arresters; Circuit breakers; Flashover; Power transformer insulation; Resistors; Samarium; Substations; Surges; Voltage; Zinc oxide;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.194002
Filename
194002
Link To Document