    Effectiveness of zinc oxide surge arresters on substation equipment probabilities of flashover

  • Author

    Lambert, Stephen R.

  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1928
  • Lastpage
    1934
  • Abstract
    Analyses indicate that significant differences can exist between effective probability of flashovers (PFOs) for a given insulation level, depending on whether surge arresters or circuit-breaker closing resistors are used to hold surges to about the same phase-to-ground levels. For phase-to-phase insulation, arresters are significantly less effective than circuit-breaker closing resistors at reducing PFOs. This is true for application of phase-to-ground arresters with or without phase-to-phase arresters. For phase-to-ground insulation, resistors are also more effective than arresters at reducing insulation requirements. This result is particularly applicable for station and line uprating and compact designs. Calculation techniques which consider phase-to-ground surges on all three phases, rather than techniques which simple consider only the phase which has the maximum surge, yield PFOs which more correctly represent the overall PFO of the insulation system
  • Keywords
    flashover; substations; surge protection; zinc compounds; ZnO surge arresters; circuit-breaker closing resistors; flashover probabilities; phase-to-ground arresters; phase-to-ground levels; phase-to-phase arresters; phase-to-phase insulation; substation equipment; Arresters; Circuit breakers; Flashover; Power transformer insulation; Resistors; Samarium; Substations; Surges; Voltage; Zinc oxide;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.194002
  • Filename
    194002