Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case
Author
Mitolo, Massimo
Author_Institution
Chu & Gassman, Middlesex, NJ
Volume
44
Issue
5
fYear
2008
Firstpage
1311
Lastpage
1316
Abstract
It seems common knowledge that three-phase short-circuit currents are the worst possible scenario for electrical systems. In reality, single-phase ground-fault currents may be significantly more intense than three-phase fault currents. With the occurrence of high single-phase fault currents, severe damage could be caused to the iron cores of electric machines included in the zero-sequence fault loop. The method of neutral low-resistance grounding will be discussed by applying a step-by-step calculation procedure to an actual case, in order to properly size the grounding resistor, thereby limiting the fault current.
Keywords
earthing; fault current limiters; power system protection; resistors; short-circuit currents; Thevenin equivalent impedance; electrical systems grounding; electrical systems neutral; fault current limiting; ground-fault currents; low-resistance grounding resistors; short-circuit currents; step-by-step calculation; zero-sequence fault loop; Fault currents; Grounding; Impedance; Industry Applications Society; Power system faults; Power system protection; Power system relaying; Protective relaying; Resistors; Voltage; Complex numbers; Thevenin equivalent impedance; ground-fault current; low-resistance neutral grounding resistor (LRG); positive-, negative-, and zero-sequence impedance; short-circuit current;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2008.2002271
Filename
4629385
Link To Document