DocumentCode
878317
Title
Triggered vacuum gaps
Author
Lafferty, J.M.
Author_Institution
General Electric Research and Development Center, Schenectady, N.Y
Volume
54
Issue
1
fYear
1966
Firstpage
23
Lastpage
32
Abstract
Characteristics of a sealed vacuum gap are described and the difficulties encountered in applying this gap as an overvoltage protection device are discussed. It is shown how these difficulties can be ameliorated by the use of gas-free electrode materials and by triggering the gap when breakdown is required. Several methods of triggering are discussed and some practical triggering devices are described that inject minute quantities of ionized hydrogen into the gap. The hydrogen is eventually recovered by the use of a titanium hydride getter. It is shown that breakdown of the gap can be accomplished in less than one-tenth microsecond by first producing a glow discharge that is rapidly transformed into a metal-vapor arc. Properties of the metal-vapor arc are described which have an effect on the characteristics of the vacuum gap. A number of practical sealed-off triggered vacuum gaps are illustrated. These are used to carry microsecond capacitor discharge currents and 60-cycle power line currents for ½ cycle. The operating voltage range is from a few hundred volts to 100 kV. The advantages of vacuum gaps over gas-filled gaps are given and a number of overvoltage protection and switching applications are listed.
Keywords
Capacitors; Electric breakdown; Electrodes; Gettering; Glow discharges; Hydrogen; Protection; Titanium; Vacuum arcs; Voltage control;
fLanguage
English
Journal_Title
Proceedings of the IEEE
Publisher
ieee
ISSN
0018-9219
Type
jour
DOI
10.1109/PROC.1966.4570
Filename
1446500
Link To Document