Abstract
Digital techniques for modelling the faulted response of any arbitrary linear shunt-reactor compensated e.h.v. transmission-line system are described. The methods are specifically developed to meet the requirements of offline or programmable test-equipment-based feeder-protection studies. The essential differences in the faulted response of single and 3-section feeders are established by reference to 500 kV interconnections involving 4-reactor linear, shunt compensators. An extensive study of modern distance protection applied to various feeder configurations is reported and the paper concludes with an evaluation of protection performance in a typical sectionalised interconnector of length 550 km.
Keywords
arcs (electric); modelling; power system interconnection; relay protection; transmission networks; voltage control; EHV feeders; arc suppression; digital techniques; distance protection; faulted response; modelling; protection performance; sectionalised interconnector; shunt reactor arrangements; voltage control;