• DocumentCode
    901848
  • Title

    Performance of distance protection of e.h.v. feeders utilising shunt - reactor arrangements for arc suppression and voltage control

  • Author

    Johns, A.T. ; El-Nour, M. ; Aggarwal, R.K.

  • Author_Institution
    University of Bath, Power Systems Laboratory, School of Electrical Engineering, Bath, UK
  • Volume
    127
  • Issue
    5
  • fYear
    1980
  • fDate
    9/1/1980 12:00:00 AM
  • Firstpage
    304
  • Lastpage
    316
  • Abstract
    Digital techniques for modelling the faulted response of any arbitrary linear shunt-reactor compensated e.h.v. transmission-line system are described. The methods are specifically developed to meet the requirements of offline or programmable test-equipment-based feeder-protection studies. The essential differences in the faulted response of single and 3-section feeders are established by reference to 500 kV interconnections involving 4-reactor linear, shunt compensators. An extensive study of modern distance protection applied to various feeder configurations is reported and the paper concludes with an evaluation of protection performance in a typical sectionalised interconnector of length 550 km.
  • Keywords
    arcs (electric); modelling; power system interconnection; relay protection; transmission networks; voltage control; EHV feeders; arc suppression; digital techniques; distance protection; faulted response; modelling; protection performance; sectionalised interconnector; shunt reactor arrangements; voltage control;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1980.0047
  • Filename
    4643276