• DocumentCode
    904099
  • Title

    Twelve-pulse back-to-back AC/DC conversion for reactive-power control

  • Author

    Arrillaga, J. ; Hyland, P.

  • Author_Institution
    University of Canterbury, Department of Electrical Engineering, Christchurch, New Zealand
  • Volume
    129
  • Issue
    5
  • fYear
    1982
  • fDate
    9/1/1982 12:00:00 AM
  • Firstpage
    206
  • Lastpage
    212
  • Abstract
    As an alternative to existing thyristor-controlled compensators, the paper proposes the use of static AC/DC power convertors for the control of reactive power. A double-bridge convertor scheme, with the two bridges operating back-to-back, is used to investigate the optimal operating conditions with respect to fundamental power and harmonic distortion. The results indicate that it is possible to maintain quasi-12-pulse operation while providirg the full range of reactive-power compensation, with and without transformers phase-shifting.
  • Keywords
    bridge circuits; compensation; electric distortion; harmonics; power control; power convertors; reactive power; back to back AC/DC conversion; double-bridge convertor scheme; harmonic distortion; reactive power control; reactive-power compensation; static AC/DC power convertors; twelve pulse operation;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1982.0034
  • Filename
    4643521