• DocumentCode
    908136
  • Title

    Modeling of out-of-step conditions in power systems

  • Author

    Kosterev, N.V. ; Yanovsky, V.P. ; Kosterev, D.N.

  • Author_Institution
    Dept. of Electr. Power Eng., Kiev Polytech. Inst., Ukraine
  • Volume
    11
  • Issue
    2
  • fYear
    1996
  • fDate
    5/1/1996 12:00:00 AM
  • Firstpage
    839
  • Lastpage
    844
  • Abstract
    Out-of-step protective relays are employed for detecting out-of-step conditions in power systems. The relay parameter setting requires simulations of expected out-of-step conditions. Here, the out-of-step conditions are modeled as a periodic motion, and are represented analytically by the Fourier series. The Fourier coefficients are computed using numerical iterations. A two-level iteration process is developed to obtain periodic bus-voltage dynamics. The computed bus voltages are then used to derive and to plot apparent impedance and line power loci needed for the out-of-step relay parameter setting. The proposed techniques are illustrated using an example of the National Power Company of Ukraine
  • Keywords
    Fourier series; iterative methods; power system analysis computing; power system protection; power system relaying; power system stability; power system transients; relay protection; Fourier coefficients; Fourier series; apparent impedance; computer simulation; line power loci; out-of-step conditions; parameter setting; periodic bus-voltage dynamics; periodic motion; power systems; protective relays; two-level iteration process; Computational modeling; Fourier series; Motion analysis; Power system analysis computing; Power system dynamics; Power system modeling; Power system protection; Power system relaying; Power system simulation; Protective relaying;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.496163
  • Filename
    496163