DocumentCode
917128
Title
Careful connection
Author
Morán, Luis T. ; Mahomar, José J. ; Dixon, Juan R.
Author_Institution
Dept. of Electr. Eng., Univ. de Concepcion, Chile
Volume
10
Issue
2
fYear
2004
Firstpage
43
Lastpage
50
Abstract
This article deals with selecting the best point of connection for shunt active power filters in multibus power distribution systems. In this article, a numerical analysis based on analytical formulation that uses the power distribution system voltage and current transfer matrices is derived providing a user friendly and general tool to determine the most adequate point of connection for shunt active filters, improving the compensation effectiveness. The validity of the developed method is verified by theory and computer simulation. The main objective of shunt active power filters is the elimination of current components that affect power distribution efficiency, such as harmonics and reactive components.
Keywords
active filters; distribution networks; harmonic distortion; industrial power systems; numerical analysis; power harmonic filters; power system harmonics; reactive power; transfer function matrices; computer simulation; connection point; current transfer matrices; harmonic component; multibus industrial power distribution steel mill plant; multibus power distribution system; numerical analysis; power distribution efficiency; reactive component; shunt active power filter; voltage sensitivity analysis; voltage transfer matrices; Active filters; Flexible AC transmission systems; Impedance; Nonlinear control systems; Power distribution; Power harmonic filters; Power system harmonics; Power system reliability; Reactive power; Voltage;
fLanguage
English
Journal_Title
Industry Applications Magazine, IEEE
Publisher
ieee
ISSN
1077-2618
Type
jour
DOI
10.1109/MIA.2004.1270801
Filename
1270801
Link To Document