• DocumentCode
    917430
  • Title

    Impact of utility switched capacitors on customer systems-magnification at low voltage capacitors

  • Author

    McGranaghan, M.F. ; Zavadil, R.M. ; Hensley, G. ; Singh, T. ; Samotyj, M.

  • Author_Institution
    Electrotek Concepts Inc., Knoxville, TN, USA
  • Volume
    7
  • Issue
    2
  • fYear
    1992
  • fDate
    4/1/1992 12:00:00 AM
  • Firstpage
    862
  • Lastpage
    868
  • Abstract
    An analysis is made of the potential for magnified transient voltages at customer buses during capacitor switching on the primary distribution system. The various factors affecting this phenomena are analyzed in detail through extensive sensitivity analysis simulations. These factors include the switched capacitor size, short-circuit capacity at the switched capacitor, customer step-down transformer size, low-voltage power factor correction, and customer load characteristics. The impact of these transients on customer equipment are described, and possible solutions to control the transients are presented
  • Keywords
    distribution networks; power capacitors; power factor correction; sensitivity analysis; short-circuit currents; switching; transients; customer load characteristics; customer step-down transformer size; customer systems; low voltage capacitors; low-voltage power factor correction; magnified transient voltages; primary distribution system; sensitivity analysis simulations; short-circuit capacity; utility switched capacitors; Circuit simulation; EMTP; Low voltage; Power capacitors; Power factor correction; Power system transients; Surges; Switched capacitor circuits; Switching circuits; Transient analysis;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.127091
  • Filename
    127091