• DocumentCode
    917604
  • Title

    Transformer winding selection associated with reconfiguration of existing double circuit line to six-phase operation

  • Author

    Stewart, James R. ; Oppel, Laurie J. ; Thomann, Gary C. ; Dorazio, Thomas F. ; Rebbapragada, R.V.

  • Author_Institution
    Power Technol. Inc., Schenectady, NY, USA
  • Volume
    7
  • Issue
    2
  • fYear
    1992
  • fDate
    4/1/1992 12:00:00 AM
  • Firstpage
    979
  • Lastpage
    985
  • Abstract
    Conversion of an existing double circuit three-phase 115 kV overhead transmission line to six-phase operation will provide a commercial demonstration of feasibility of high phase order power transmission. An important part of this demonstration is specification of the phase/voltage conversion transformers and requirements to permit single pole switching of the line in a practical manner at minimum cost. Results are presented of engineering studies which led to selection of two delta-wye three-phase transformers at each end, one of each pair with reversed polarity to obtain the 60° shift between phases
  • Keywords
    phase convertors; power convertors; power overhead lines; power transformers; switching; transformer windings; 115 kV; cost; delta-wye; overhead transmission line; phase convertors; power convertors; power transmission; single pole switching; six-phase; three-phase; transformers; winding selection; Circuit simulation; Coupling circuits; Impedance; Leg; Magnetic analysis; Magnetic switching; Switches; Switching circuits; Voltage; Windings;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.127107
  • Filename
    127107