DocumentCode
937272
Title
Fault-location algorithm for multiphase power lines
Author
Ibe, A.O. ; Cory, B.J.
Author_Institution
Anambra State University, Department of Electrical Engineering, Enugu, Nigeria
Volume
134
Issue
1
fYear
1987
fDate
1/1/1987 12:00:00 AM
Firstpage
43
Lastpage
50
Abstract
Improved mathematical models of transmission lines are used to develop a fault location method which copes with high-frequency transients. The telegraph equations used for a line model are solved by the method of characteristics using voltage and current samples as boundary conditions taken at one end of the line within the first few milliseconds of fault inception. Estimates of voltage and current profiles for the entire length of the transmission line during the fault are obtained. Criteria for fault location are based on a formulation involving these voltage and current estimates. For fault location on multiphase systems the concept of modal analysis is used in enhancing the fault-locating capability of this algorithm.
Keywords
fault location; power transmission lines; transients; fault location method; high-frequency transients; modal analysis; multiphase power lines; telegraph equations; transmission lines;