• DocumentCode
    942658
  • Title

    Method for in-field evaluation of the stator winding connection of three-phase induction motors to maximize efficiency and power factor

  • Author

    Ferreira, Fernando J T E ; De Almeida, Anibal T.

  • Author_Institution
    Dept. of Electr. Eng., Eng. Inst. of Coimbra, Portugal
  • Volume
    21
  • Issue
    2
  • fYear
    2006
  • fDate
    6/1/2006 12:00:00 AM
  • Firstpage
    370
  • Lastpage
    379
  • Abstract
    The performance of the oversized three-phase induction motors can be improved, both in terms of efficiency and power factor, with the proper change of the stator winding connection, which can be delta or star, as a function of their load. A practical method is proposed to quickly and easily evaluate which stator winding connection is more appropriate for the actual motor load profile, in order to increase the motor efficiency and power factor. This new method is suitable for in-field evaluation, because it requires only the use of inexpensive equipment and has enough accuracy to allow a proper decision to be made. The automatic change of the stator winding connection, as a function of the motor line current, is also analyzed. When properly applied, these methods can lead to the improvement of the efficiency and power factor of permanently oversized motors, motors with a load variation between low load and near full load during their duty cycle, and/or motors driving high-inertia, low duty cycle loads. The proposed methods are particularly suitable to industrial plants where typically many electric motor systems are oversized and/or can have a wide load variation. In these conditions, the active and reactive electrical energy bill can be significantly reduced.
  • Keywords
    induction motors; power factor; reactive power; stators; industrial plants; infield evaluation; motor load profile; power factor; reactive electrical energy bill; stator winding connection; three-phase induction motor; Electric motors; Electrical equipment industry; Induction motors; Industrial plants; Load management; Manufacturing industries; Power engineering and energy; Reactive power; Service robots; Stator windings; Energy efficiency; motor oversizing; power factor; savings; stator winding connection change; three-phase induction motor;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/TEC.2006.874248
  • Filename
    1634583