DocumentCode
967715
Title
High-Current Arc Gap With Ablative Wall: Dielectric Recovery and Wall-Contact Interaction
Author
Lee, A. ; Heberlein, J.V.R. ; Meyer, T.N.
Author_Institution
Westinghouse Reasearch and Development Center, Pittsburgh, PA, USA
Volume
8
Issue
1
fYear
1985
fDate
3/1/1985 12:00:00 AM
Firstpage
129
Lastpage
134
Abstract
The purpose of this study is to examine the effects of wallmaterial ablation and contact materials on the recovery of an arc gap. A capacitive discharge current source provides 60-Hz arc currents up to 8 kA, and recovery is measured by reapplyiag a voltage step of 1 kV at a preselected time after current zero. The arc gap is surrounded by a cylindrical wall of an ablative insulating material. Both contact and wall materials are varied. We find strong dependence of the recovery time on the contact and wall material. For our geometry we observe fastest recovery at a current of approximately 5 kA, independent of wall materials. The interaction of ablated wall-material vapor with the contact material has been observed to degrade gap recovery performance and enhance contact erosion.
Keywords
Ablation; Contacts; Interrupters; Contacts; Current measurement; Degradation; Dielectric materials; Fault location; Geometry; Insulation; Magnetic materials; Research and development; Time measurement;
fLanguage
English
Journal_Title
Components, Hybrids, and Manufacturing Technology, IEEE Transactions on
Publisher
ieee
ISSN
0148-6411
Type
jour
DOI
10.1109/TCHMT.1985.1136475
Filename
1136475
Link To Document