3-D FEM Analysis of Effect of Twist Pitch and Shielding Layer on Multi-Layered HTS Power Cable
Author
Miyagi, Daisuke ; Takahashi, Norio ; Torii, Shinji ; Ueda, Kiyotaka ; Yasuda, Kenji
Author_Institution
Dept. of Electr. & Electron. Eng., Okayama Univ.
Volume
16
Issue
2
fYear
2006
fDate
6/1/2006 12:00:00 AM
Firstpage
1614
Lastpage
1617
Abstract
3-D finite element analysis of current distribution taking account of the nonlinear E-J characteristic is carried out. In order to study the ac loss of multi-layered HTS power cable, the analysis region is considerably reduced by modeling spirally wound superconducting tapes as conductors having an anisotropic conductivity and using the periodic boundary condition. By using this model, the effect of the twist pitch on the current distribution of multi-layered HTS power cable with a shield layer is illustrated and the structure with low ac loss is discussed
Keywords
cable shielding; current distribution; finite element analysis; high-temperature superconductors; losses; multilayers; superconducting cables; superconducting tapes; 3-D finite element analysis; AC loss; anisotropic conductivity; current distribution; multilayered high-temperature superconducting power cable; nonlinear E-J characteristics; periodic boundary condition; shielding layer; spirally wound superconducting tapes; twist pitch; Anisotropic magnetoresistance; Boundary conditions; Conductivity; Conductors; Current distribution; Finite element methods; High temperature superconductors; Power cables; Superconducting films; Wounds; 3-D Finite element analysis; AC loss; HTS shield; multi-layered HTS power cable;
fLanguage
English
Journal_Title
Applied Superconductivity, IEEE Transactions on
Publisher
ieee
ISSN
1051-8223
Type
jour
DOI
10.1109/TASC.2005.864282
Filename
1643167
Link To Document