An ATP-EMTP-based model for analysis of shielding properties of ferromagnetic cable sheaths
Author
Popov, Marjan ; Grcev, Leonid ; Van der Sluis, Lou ; Terzija, Vladimir V.
Author_Institution
Power Syst. Lab., Delft Univ. of Technol., Netherlands
Volume
20
Issue
3
fYear
2005
fDate
7/1/2005 12:00:00 AM
Firstpage
2241
Lastpage
2247
Abstract
Ferromagnetic materials, such as steel, are used for shielding of power and telecommunication cables. These shields often provide path for currents during faults or lightning and are important for the integrity and safety of electrical systems and devices. Since such currents might be with low- or high-frequency content, and of low or high intensity, ferromagnetic shield behavior might be quite different due to hysteresis. This paper describes a method for analyzing the dynamic behavior of ferromagnetic cable shields based on the Jiles model of hysteresis. The solution is implemented in ATP-EMTP, which allows one to analyze the complex behavior of ferromagnetic cable shields in conjunction with that of the other elements of the power system. Due to limitations of the model of hysteresis, application of the proposed model is limited to frequencies up to about 10 kHz. The model is illustrated for a practical 100-m-long cable.
Keywords
EMTP; cable sheathing; cable shielding; ferromagnetic materials; hysteresis; safety; 100 m; ATP-EMTP; Jiles model; electrical system safety; ferromagnetic cable sheaths; ferromagnetic materials; hysteresis; shielding properties; Cable shielding; Electrical safety; Hysteresis; Lightning; Magnetic materials; Power cables; Power system dynamics; Power system modeling; Safety devices; Steel; ATP-EMTP; Jiles model; MODELS; cable; hysteresis; magnetic field;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.843398
Filename
1458903
Link To Document