• DocumentCode
    989105
  • Title

    Onsite MOSA condition Assessment-a new approach

  • Author

    Karawita, Chandana ; Raghuveer, M.R.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Manitoba, Winnipeg, Canada
  • Volume
    21
  • Issue
    3
  • fYear
    2006
  • fDate
    7/1/2006 12:00:00 AM
  • Firstpage
    1273
  • Lastpage
    1277
  • Abstract
    A new method to assess the condition of metal-oxide surge arresters is presented. The fundamental component of the resistive current is used as an indicator. This current is obtained by exploiting the linear relationship, which exists between the peak value of the fundamental component of the resistive current and the phase shift between the fundamental components of the capacitive current and the total arrester current. This relationship is independent of temperature for a given type of arrester. Results are presented to demonstrate the accuracy and the reliability of the new technique.
  • Keywords
    arresters; MOSA; metal-oxide surge arrester; phase shift; resistive current; total arrester current; Aging; Arresters; Current measurement; Electromagnetic measurements; Partial discharges; Power system protection; Power system reliability; Probes; Surge protection; Voltage; Diagnostic indicator; metal-oxide surge arrester (MOSA); resistive current;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2005.860264
  • Filename