• DocumentCode
    992427
  • Title

    Parallel Operation of Transformers Whose Ratios of Transformation are Unequal

  • Author

    Macferran, Mabel

  • Author_Institution
    Operating Department, Southern California Edison Company.
  • Volume
    49
  • Issue
    1
  • fYear
    1930
  • Firstpage
    125
  • Lastpage
    131
  • Abstract
    An equation is developed for use in meeting emergency conditions which necessitate the paralleling of transformer banks whose impedances expressed in percentage form are not equal. This equation makes it possible to calculate what change should be made in the ratio of transformation of the bank with the lower percentage impedance in order to prevent its being overloaded when the total load approaches the combined capacity of the two banks. It is pointed out that such an expedient is a makeshift justifiable only when maintenance of service is the paramount consideration and efficiency is, for the time being, of secondary importance. When conditions arise which do justify such a temporary arrangements ment, the method developed in the present paper affords a simple, yet accurate, means of solving the problem.
  • Keywords
    Circuits; Costs; Equations; Impedance; Phase measurement; Phase transformers;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1930.5055467
  • Filename
    5055467