• DocumentCode
    998382
  • Title

    Development of 550 kV 1-break GCB. II. Development of prototype

  • Author

    Toda, H. ; Kobayashi, A. ; Takagi, H. ; Suzuki, K. ; Ikeda, H. ; Murayama, Y.

  • Author_Institution
    Toshiba Corp., Kawasaki, Japan
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    7/1/1993 12:00:00 AM
  • Firstpage
    1192
  • Lastpage
    1198
  • Abstract
    For pt.I see ibid., vol.8, no.3, p.1189-91, 1993. The development of a 550 kV 1-break gas blast circuit breaker is described. To reduce drive energy and sliding speed a new drive system, in which a contact conventionally fixed is moved in the direction opposite to the movement of movable contact, was adopted. As a result, size reduction becomes possible while maintaining reliability. It is also found that applying this 1-break gas circuit breaker to gas insulated switchgear greatly reduces its size.<>
  • Keywords
    electrical contacts; gas blast circuit breakers; gaseous insulation; reliability; 550 kV; GIS; contact; development; drive energy; gas blast circuit breaker; gas insulated switchgear; reliability; size; sliding speed;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.252644
  • Filename
    252644