• Title of article

    Use of district heating in summer for cold production with the aid of an absorption process

  • Author/Authors

    Ch Mostofizadeh، نويسنده , , D Bohne، نويسنده , , Ch Mergardt، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    10
  • From page
    577
  • To page
    586
  • Abstract
    The possibility of using district heating for cold production for lower cold capacities was investigated. A function model with a cold capacity of 50 kW was set up which operates according to the principle of single-effect absorption and manages with low supply temperatures (80 °C). A compact layout was achieved by installing plate packages. Numerous measurements show that the layout examined displays a stable operating behavior and achieves a COP factor of about 0.8. At part-load >20% the COP factor is on the order of magnitude of 0.6.
  • Keywords
    Single-effect absorption , District heating , Lower cold capacity , Lower supply temperature
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2002
  • Journal title
    Applied Thermal Engineering
  • Record number

    1023455