Title of article :
Thermoeconomic analysis of a cogeneration system of a university campus
Author/Authors :
José Luz Silveira، نويسنده , , A Beyene، نويسنده , , E.M Leal، نويسنده , , J.A Santana، نويسنده , , D Okada، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
13
From page :
1471
To page :
1483
Abstract :
In this paper, a thermoeconomic analysis method based on the First and the Second Law of Thermodynamics and applied to analyse the replacement of an equipment of a cogeneration system is presented. The cogeneration system consists of a gas turbine linked to a waste boiler. The electrical demand of the campus is approximately 9 MW but the cogen system generates approximately one third of the university requirement as well as 1.764 kg/s of saturated steam (at 0.861 MPa), approximately, from a single fuel source. The energy-economic study showed that the best system, based on pay-back period and based on the maximum savings (in 10 years), was the system that used the gas turbine “M1T-06” of Kawasaki Heavy Industries and the system that used the gas turbine “CCS7” of Hitachi Zosen, respectively. The exergy-economic study showed that the best system, which has the lowest EMC, was the system that used the gas turbine “ASE50” of Allied Signal.
Keywords :
Gas turbine , Cogeneration , Exergetic manufacturing cost , Energy-economic analysis
Journal title :
Applied Thermal Engineering
Serial Year :
2002
Journal title :
Applied Thermal Engineering
Record number :
1023530
Link To Document :
بازگشت