Title of article :
Experimental investigation on the performance of air cooler under frosting conditions
Author/Authors :
Dong-quan Deng، نويسنده , , Lie Xu، نويسنده , , Shi-qiong Xu، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
8
From page :
905
To page :
912
Abstract :
Evaluation of heat transfer performance of the air cooler under frosting conditions is of great importance for the refrigeration industry. In this paper, effects of frost growth on the performance of the air cooler have been studied with an experimental air cooler of industrial size with different fin spacings, i.e., 6, 8 and 10 mm. Results showed that factors affecting the heat transfer performance of the air cooler include the evaporation temperature, the frost height, the fin spacing and the air velocity. The overall heat transfer coefficients based on a logarithmic mean temperature difference (LMTD) and the energy transfer coefficients based on a logarithmic mean enthalpy difference (LMED) were calculated. As the frost accumulated on the air cooler, the overall heat transfer coefficient and energy transfer coefficient will drop gradually
Keywords :
Air cooler , Frost , Overall heat transfer coefficient , Energy transfer coefficient
Journal title :
Applied Thermal Engineering
Serial Year :
2003
Journal title :
Applied Thermal Engineering
Record number :
1023724
Link To Document :
بازگشت