Title of article :
Experimental study of the effect of winglet location on heat transfer enhancement and pressure drop in fin-tube heat exchangers
Author/Authors :
S.M. Pesteei، نويسنده , , P.M.V. Subbarao، نويسنده , , R.S. Agarwal، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
13
From page :
1684
To page :
1696
Abstract :
Local heat transfer coefficients were measured on fin-tube heat exchanger with winglets using a single heater of 2 inch diameter and five different positions of winglet type vortex generators. The measurements were made at Reynolds number about 2250. Flow losses were determined by measuring the static pressure drop in the system. Results showed a substantial increase in the heat transfer with winglet type vortex generators. It has been observed that average Nusselt number increases by about 46% while the local heat transfer coefficient improves by several times as compared to plain fin-tube heat exchanger. The maximum improvement is observed in the re-circulation zone. The best location of the winglets was with ΔX = 0.5D and ΔY = 0.5D. The increase in pressure drop for the existing situation was of the order of 18%.
Keywords :
Heat exchanger , Vortex generators , Winglets , Heat transfer enhancement , Longitudinal vortices
Journal title :
Applied Thermal Engineering
Serial Year :
2005
Journal title :
Applied Thermal Engineering
Record number :
1026131
Link To Document :
بازگشت