Title of article :
Experimental studies on HFC based two-stage half effect vapour absorption cooling system
Author/Authors :
S. Arivazhagan، نويسنده , , R. Saravanan، نويسنده , , S. Renganarayanan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Pages :
8
From page :
1455
To page :
1462
Abstract :
An experimental investigation on the performance of a two-stage half effect vapour absorption cooling system has been carried out and presented. The prototype is designed for 1 kW cooling capacity using HFC based working fluids (R134a as refrigerant and DMAC as absorbent). The performance of the system in terms of degassing range, coefficient of performance and second law efficiency has been obtained. The system is capable of producing evaporating temperature as low as −7 °C with generator temperatures ranging from 55 to 75 °C. The degassing range is 40% more in high absorber than in low absorber as the high absorber is operated at optimum intermediate pressure. The optimum generator temperature is found to be in the range of 65–70 °C at which the coefficient of performance is 0.36.
Keywords :
Degassing range , Circulation ratio , Two-stage half effect cycle , Coefficient of performance , HFC based working fluids
Journal title :
Applied Thermal Engineering
Serial Year :
2006
Journal title :
Applied Thermal Engineering
Record number :
1040679