Title of article :
A complete model of wet cooling towers with fouling in fills
Author/Authors :
Bilal A. Qureshi، نويسنده , , Syed M. Zubair، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Abstract :
A cooling tower basically consists of three zones; namely, spray zone, packing and rain zones. In cooling towers, a significant portion of the total heat rejected may occur in the spray and rain zones. These zones are modeled and solved simultaneously using engineering equation solver (EES) software. The developed models of these zones are validated against experimental data. For the case study under consideration, the error in calculation of the tower volume is 6.5% when the spray and rain zones are neglected. This error is reduced to 3.15% and 2.65% as the spray and rain zones are incorporated in the model, respectively. Furthermore, fouling in cooling tower fills as well as its modeling strategy is explained and incorporated in the cooling tower model to study performance evaluation problems. The fouling model is presented in terms of normalized fill performance index (ηF,norm) as a function of weight gain due to fouling. It is demonstrated that the model is asymptotic, which is similar to typical asymptotic fouling model used in conventional heat exchangers.
Keywords :
Spray zone , Rain zone , Cooling tower , Fouling
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering