Title of article :
In-tube passive heat transfer enhancement in the process industry
Author/Authors :
Leon Liebenberg، نويسنده , , Josua P. Meyer، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
14
From page :
2713
To page :
2726
Abstract :
Enhanced heat transfer surfaces are used in heat exchangers to improve performance and to decrease system volume and cost. In-tube heat transfer enhancement usually takes the form of either micro-fin tubes (of the helical micro-fin or herringbone varieties), or of helical wire inserts. Despite a substantial increase in heat transfer, these devices also cause non-negligible pressure drops. By making use of well-proven flow pattern maps for smooth tubes and the new ones for smooth and enhanced tubes, it is shown from the refrigerant condensation data that flow patterns have a strong influence on heat transfer and pressure drop. This is done for data obtained from in-tube condensation experiments for mass fluxes ranging from 300 to 800 kg/m2 s at a saturation temperature of 40 °C, for refrigerants R-22, R-134a, and R-407C. The flow regimes, pressure drops, heat transfer coefficients, and the overall performance of three different tubes, namely a smooth-, 18° helical micro-fin-, and a herringbone micro-fin tube (each having a nominal diameter of 9.51 mm), are presented and compared to the performance of smooth tubes with helical wire inserts (with pitches of 5 mm, 7.77 mm and 11 mm corresponding to helical angles of 78.2°, 72°, and 65.3°, respectively).
Keywords :
Flow pattern maps , Enhanced heat transfer , Refrigerant condensation
Journal title :
Applied Thermal Engineering
Serial Year :
2007
Journal title :
Applied Thermal Engineering
Record number :
1041468
Link To Document :
بازگشت